Home >Product list >High voltage circuit breaker test equipment > TE3600 High Precision High Current Microhmmeter
TE3600 High Precision High Current Microhmmeter
 
Product Manuals
Related downloads
Technical Data
Picture    Collect
TE3600 High Precision High Current Microhmmeter
TE3600 Series High Precision High Current Microhmmeter, with the features of high current, anti-jamming, high intelligent, portable and easy to operate, it is widely used loop resistance test, with the resolution of 0.01μΩ , can output high current lastingly, and overcome the shortcomings of pulse power supply can not continuous supply power and cannot effectively breakdown oxide film.
Product Feature

  (1) Adopt the latest power supply technology, can output high current lastingly, and overcome the shortcomings of pulse power supply can only momentary output current, can effectively breakdown switch oxide film, and obtain the accurate test results.
  (2) The data can be stabilized at 0.01μΩ under the serious interference environment, with good data reproducibility, and according to the size of test product automatic switching range, particularly suitable for micro-resistance high-precision test.
  (3) The output values and time of current can selected automatically through available software, without regulator, or potentiometer adjustment, the adjustment of mechanical wear parts will not cause equipment failure.
  (4) The perfect combination of large current and portability, 600A device weighs just 12kg; new Chinese input method to realize the data humane, intelligent management.
  (5) Unique hardware and software design, which can eliminate the effect of test lead resistance and test clamp contact resistance on the test results. There is no impact to change the length of test leads.

Technical Parameters
 Power Supply   Voltage:AC220V±10%     Frequency:50Hz±1Hz
 Dimensions   Length440mm*Width330mm*Height235mm
 Weight   12Kg
 Service condition   Ambient temperature:-10℃~40℃   Relative humidity:≤80%
 Instrument power   The rated power of the instrument <3000w
 Measurement range   0μΩ~1000μΩ
 Measurement Accuracy   The Measurement Accuracy of the instrument is ±(1%×reading+2μΩ)
 Maximum resolution   The Maximum resolution of the instrument is 0.01μΩ
 Test current   The test current of the instrument is 100A、 200A 、400A and 600A selective.
 Continuous output current time   100A: 10s~600s
  200A: 10s~600s
  400A: 10s~60s
  600A: 10s

 

 

  